Description
| eClass-No.: | 37010203 |
| Application: | Selection criteria: simple control task, non-critical operating conditions, standard requirements Application: industrial complex, building technology,mechanical engineering |
| Medium: | Cooling water, cooling brine, warm water, hot water, steam, gas, etc. |
Features
• Compact design
• Precision guided stem
• Burnished stem
• Tapered seat ring
• 2 screwed seatrings
• Reducible kvs-values
• Rangeability 30 : 1
• Post guided plug
• EPDM sealing
• Travel indicator
Technical data
| Figure | Nominal pressure | Material | Nominal diameter | Information / restriction of technical rules need to be observed! A production permission acc. to TRB 801 No. 45 is available.
The engineer, designing a system or a plant, is responsible for the selection of the correct valve. Resistance and fitness must be verified, contact manufacturer for information (refer to Product overview and Resistance list). |
| 35.453 | PN40 | 1.0619+N | DN25 – 100 | |
|
Other materials and versions on request. |
||||
| Pressure-temperature-ratings | Intermediate values for max. permissible operational pressures can be determined by linear interpolation of the given temperature / pressure chart. |
| acc. to manufacturers standard | -10°C to 120°C | 150°C | 180°C |
| 1.0619+N PN40 (bar) | 40 | 38,1 | 36,2 |
| Operation |
| The feedwater control valve regulates the flow of feedwater to the steam boiler.
It is controlled by a level controller. The target of the control is to keep the level in the boiler constant. The feedwater control valve is normally built into the feed water pressure line. If the water level drops in the boiler, the electrical actuator PREMIO-Plus 2G adjustes a perforated plug in the valve. If the water level in the boiler rises, the perforated plug closes the seat. Once the feed water amount to the boiler falls below a certain amount, a further perforated plug opens the bypass valve. It ensures that the minimum amount, required for cooling and lubrication of the feed water pump, is always available. |
| Necessary data for sizing |
| Medium: Feed water
Temperature: …………………… [°C] Inlet pressure: …………………… [bar(g)] (Pump pressure ) After-pressure: …………………… [bar(g)] (Boiler pressure) Boiler capacity: …………………… [t/h] Pump delivery rate: …………………… [m³/h] Recirculation flowrat: …………………… [m³/h] Actuator PREMIO-Plus 2G: Voltage: …………………… Options: …………………… |
| Closing pressures refer to page 5. |
| DN | 25 | 32 | 40 | 50 | 65 | 80 | 100 |
| Fig. 453 | 2,2 kN | H | (mm) | 563 | 589 | 595 | 593 | — | — | — |
| PN40 | (kg) | 14 | 18 | 22 | 25 | — | — | — | ||
| 5 kN | H | (mm) | 563 | 589 | 595 | 593 | 629 | 645 | 664 | |
| PN40 | (kg) | 15 | 19 | 22 | 25 | 34 | 45 | 63 | ||
| 12 kN | H | (mm) | 737 | 763 | 769 | 767 | 803 | 819 | 838 | |
| PN40 | (kg) | 20 | 23 | 27 | 30 | 39 | 49 | 68 | ||
| 15 kN | H | (mm) | — | — | — | — | 803 | 819 | 838 | |
| PN40 | (kg) | — | — | — | — | 39 | 49 | 68 |
| DN | 25 | 32 | 40 | 50 | ||||||||||||||||
|
Straight through |
Kvs-value | (m3/h) | 1 | 1,6 | 2,5 | 4 | 6,3 | 2,5 | 4 | 6,3 | 10 | 4 | 6,3 | 10 | 16 | 6,3 | 10 | 16 | 25 | |
| Seat-Ø A | (mm) | 27 | 27 | 31 | 27 | 31 | 41 | 27 | 31 | 41 | 51 | |||||||||
|
Bypass |
Kvs-value | (m3/h) | 0,1 | 0,16 | 0,25 | 0,40 | 0,63 | 0,25; | 0,4 | 0,63 | 1,0 | 0,4 | 0,63 | 1,0 | 1,6 | 0,63 | 1,0 | 1,6 | 2,5 | |
| Seat-Ø B | (mm) | 8 | 8 | 8 | 13 | 8 | 13 | |||||||||||||
| max. differential pressure 1) | (bar) | 40 | 40 | 40 | 40 | |||||||||||||||
| Travel | (mm) | 20 | 20 | 20 | 20 | |||||||||||||||
|
2,2 kN |
Closing pressure | I. | (bar) | 15,4 | 15,4 | 11,6 | 15,4 | 11,6 | 6,4 | 15,4 | 11,6 | 6,4 | 4 | |||||||
| Operating time | (s) | 53 | 53 | 53 | 53 | |||||||||||||||
| Operating speed 2) | (mm/s) | 0,38 | ||||||||||||||||||
|
5 kN |
Closing pressure | I. | (bar) | 38,5 | 38,5 | 29,2 | 38,5 | 29,2 | 16,6 | 38,5 | 29,2 | 16,6 | 10,6 | |||||||
| Operating time | (s) | 53 | 53 | 53 | 53 | |||||||||||||||
| Operating speed | (mm/s) | 0,38 | ||||||||||||||||||
|
12 kN |
Closing pressure | I. | (bar) | 40 | 40 | 40 | 40 | 27,2 | ||||||||||||
| Operating time | (s) | 53 | 53 | 53 | 53 | |||||||||||||||
| Operating speed | (mm/s) | 0,38 | ||||||||||||||||||
| DN | 65 | 80 | 100 | ||||||||||||
|
Straight through |
Kvs-value | (m3/h) | 10 | 16 | 25 | 40 | 16 | 25 | 40 | 63 | 25 | 40 | 63 | 100 | |
| Seat-Ø A | (mm) | 41 | 41 | 51 | 66 | 41 | 51 | 66 | 81 | 51 | 66 | 81 | 101 | ||
|
Bypass |
Kvs-value | (m3/h) | 1,0 | 1,6 | 2,5 | 4 | 1,6 | 2,5 | 4,0 | 6,3 | 2,5 | 4,0 | 6,3 | 10 | |
| Seat-Ø B | (mm) | 25 | 25 | 25 | |||||||||||
| max. differential pressure 1) | (bar) | 40 | 40 | 40 | |||||||||||
| Travel | (mm) | 30 | 30 | 30 | |||||||||||
|
5 kN |
Closing pressure | I. | (bar) | 16,5 | 16,5 | 10,5 | 6,2 | 16,5 | 10,5 | 6,2 | 4 | 10,5 | 6,2 | 4 | 2,5 |
| Operating time | (s) | 79 | 79 | 79 | |||||||||||
| Operating speed | (mm/s) | 0,38 | |||||||||||||
|
12 kN |
Closing pressure | I. | (bar) | 40 | 40 | 27,1 | 16,1 | 40 | 27,1 | 16,1 | 10,6 | 27,1 | 16,1 | 10,6 | 6,8 |
| Operating time | (s) | 79 | 79 | 79 | |||||||||||
| Operating speed | (mm/s) | 0,38 | |||||||||||||
|
15 kN |
Closing pressure | I. | (bar) | 40 | 40 | 34,3 | 20,4 | 40 | 34,3 | 20,4 | 13,4 | 34,3 | 20,4 | 13,4 | 8,6 |
| Operating time | (s) | 79 | 79 | 79 | |||||||||||
| Operating speed | (mm/s) | 0,38 | |||||||||||||
| Further operating speeds: refer to data sheet ARI-PREMIO / PREMIO-Plus 2G | |||||||||||||||
ARI-STEVI® Pro 453
Feedwater control valve – 3-way with flanges – with pump spill back
PHONE: 0812-3340-4116WHATSAPP: 0812-3340-4116
ARI ARMATUREN – Steam product solutions
- ARI-STEVI® Pro 470 / 471 (DN15-150) Control valve
- ARI-STEVI® Pro 470 / 471 – ANSI (DN25-200) Control valve
- ARI-STEVI® Pro 422 / 462 (DN200-250) Control valve
- ARI-STEVI® Vario 448 / 449 (DN15-100) Control valve
- ARI-STEVI® 440 / 441 (DN15-250) Control valve ARI Armaturen
- ARI-STEVI® 425 / 426 (DN300-500) Control valve ARI Armaturen
- ARI-STEVI® 450 / 451 (DN15-150) Control valve
- ARI-STEVI® Smart 423 / 463 (DN200-300) Control valve
- ARI-STEVI® Pro 453 Feedwater control valve
- ARI-STEVI® 405 / 460 (DN15-500) Stop valve