ARI-TEMPTROL® 773/774

Thermal-mixing/diverting valve – 3way with flanges without cooling spacer (max. 150°C)

ARI-TEMPTROL® 773/774 Thermal-mixing/diverting valve - 3way with flanges without cooling spacer (max. 150°C)
eClass-No.: 37012290
Application: Industrial heating and ventilation systems, residential applications, marked-warehouses, ship building, cooling systems, etc.
Medium: Fluids, air and steam

Thermal-mixing/diverting valve – 3way with flanges

ARI-TEMPTROL® 773/774Thermal-mixing/diverting valve – 3way with flanges without cooling spacer (max. 150°C)

Fig. …773 max. 150°C


ARI-TEMPTROL® 773/774Thermal-mixing/diverting valve – 3way with flanges without cooling spacer (max. 150°C)

Fig. …774 with cooling spacer max. 300°C

Figure Nominal pressure Material Nominal diameter
12.773 / 12.774 PN16 EN-JL1040 DN15-100
22.773 / 22.774 PN16 EN-JS1049 DN15-100
23.773 / 23.774 PN25 EN-JS1049 DN15-100
35.773 / 35.774 PN40 1.0619+N DN15-100
55.773 / 55.774 PN40 1.4408 DN15-100

ARI-TEMPTROL® 773/774 Thermal-mixing/diverting valve – 3way with flanges without cooling spacer (max. 150°C)

Figure Nominal pressure Material Nominal diameter
12.773….1..1 12.774….1..1 PN16 EN-JL1040 DN15-50

ARI-TEMPTROL® 773/774Thermal-mixing/diverting valve – 3way with flanges without cooling spacer (max. 150°C)

Fig. 12.773….1..1 max. 130°C


ARI-TEMPTROL® 773/774Thermal-mixing/diverting valve – 3way with flanges without cooling spacer (max. 150°C)

Fig. 12.774….1..1 with cooling spacer max. 250°C

DN 15 20 25 32 40 50 65 80 100
Face-to-face dimension FTF series 1 according to DIN EN 558 Standard-flange dimensions refer to page 15.
L (mm) 130 150 160 180 200 230 290 310 350
Dimensions
Fig. 773 H (mm) 195 195 200 225 245 280 300 365 385
Fig. 774 H (mm) 340 340 345 370 390 425 445 510 530
Fig. 773….1..1 (LC) H (mm) 125 125 130 155 160 160 — — —
Fig. 774….1..1 (LC) H (mm) 270 270 275 300 305 305 — — —
Weights
Fig. 773 (kg) 4,4 5,8 7,6 9,9 14,5 16,5 25 31 38
Fig. 774 (kg) 5,4 6,8 8,6 10,9 15,5 17,5 26 32 39
Fig. 773….1..1 (LC) (kg) 3,5 5 6,5 8,5 12,5 14 — — —
Fig. 774….1..1 (LC) (kg) 4,5 6 7,5 9,5 13,5 15 — — —
Kvs-value
Standard Kvs-value (m3/h) 4,0 6,3 10,0 16,0 22,0 32,0 50,0 70,0 80,0
Travel (mm) 7,5 7,5 8 9,5 9,5 11,5 14 15 15
Reduced Kvs-value (m3/h) 1,0 — — — — — — — —
Travel (mm) 5 — — — — — — — —
Max. differential pressure drop Δp
Fig. 773 Fig. 774 Mixing function pB > pA (Δp = pB – pAB) (bar) 12 16 16 16 12 9 9 9 9
 

pA > pB (Δp = pA – pAB)

(bar) 12 4 4 4 4 4 4 4 4
Diverting function  

pAB > pB pAB > pA

(bar) 12 4 4 4 3 1,5 0,7 0,25 0,15
Fig. 773….1..1 (LC) Fig. 774….1..1 (LC) Mixing function (bar) 3 3 2,5 1,5 1 0,5 — — —
Diverting function (bar) 3 3 2,5 1,5 1 0,5 — — —
Pressure balancing of the actuator needed at P1 > max. differential pressure drop Δp (out of table). For pressure balancing use manual control device (Type 9900390011).
Parts
Pos. Sp.p. Description Fig. 12.773 Fig. 12.774 Fig. 22./23.773 Fig. 22./23.774 Fig. 35.773 Fig. 35.774 Fig. 55.773 Fig. 55.774
1 Body EN-JL1040, EN-GJL-250 EN-JS1049,

EN-GJS-400-18U-LT

GP240GH+N, 1.0619+N GX5CrNiMo19-11-2, 1.4408
1.2 Seat X20Cr13+QT, 1.4021+QT X6CrNiMoTi17-12-2, 1.4571
3 Cheese head screw A2-70
4 x Plug guiding X20Cr13+QT, 1.4021+QT X6CrNiTi18-10, 1.4541
5 Giude bushing X20Cr13+QT, 1.4021+QT X6CrNiTi18-10, 1.4541
7 x Gasket Graphite
11 Bonnet EN-JS1049, EN-GJS-400-18U-LT GX5CrNiMo19-11-2, 1.4408
14 x Spindle unit X20Cr13+QT, 1.4021+QT / X6CrNiTi18-10, 1.4541 X6CrNiTi18-10, 1.4541
19 Bearing cover X6CrNiTi18-10, 1.4541
21 Hexagon nut A2-70
28 Cooling spacer EN-JS1049, EN-GJS-400-18U-LT X6CrNiTi18-10, 1.4541
37 x Compression spring X12CrNi17-7, 1.4310
55 x Balanced bellow X6CrNiTi18-10, 1.4541
└ Spare parts

Information / restriction of technical rules need to be observed!

Operating and installation instructions can be downloaded at www.ari-armaturen.com. ARI-Valves of EN-JL1040 are not allowed to be operated in systems acc. to TRD 110.

A production permission acc. to TRB 801 No. 45 is available (acc. to TRB 801 No. 45 EN-JL1040 is not allowed.) The engineer, designing a system or a plant, is responsible for the selection of the correct valve.

Resistance and fitness must be verified (contact manufacturer for information, refer to Product overview and Resistance list).

©2022 PT. TOTALITAS TEKNIK INDONESIA. All Rights Reserved.