ARI-STEVI® Smart 423 / 463 (DN200-300)

Control valve – 3-way with flanges

eClass-No.: 37010213
Application: Selection criteria: simple control task, non-critical operating conditions, standard requirements
Application: industrial complex, building technology,mechanical engineering
Medium: Cooling water, cooling brine, warm water, hot water, steam, gas, etc.

The control valves are especially suitable for actuation by pneumatic or electrical actuators.
Depending on the mode of operation, two different execution methods are possible:
1. Execution with mixing plug
2. Execution with diverting plug
The execution with the mixing plug is the standard execution method.
This execution method is to be chosen when the valve is also employed as a mixer
(2 entrances, 1 exit.)
In exceptional cases, the execution with the mixing plug can also be employed as a
diverting plug (1 entrance, 2 exits). This requires, however, low differential pressures and
stable propulsion.
The execution method with the diverting plug is only to be employed with the operation of
diverting.

Figure Nominal pressure Material Nominal diameter Information / restriction of technical rules need to be observed!

ARI-Valves of EN-JL1040 are not allowed to be operated in systems acc. to TRD 110.

A production permission acc. to TRB 801 No. 45 is available. (Acc. to TRB 801 No. 45 EN-JL1040 is not allowed.)

The engineer, designing a system or a plant, is responsible for the selection of the correct valve.

Resistance and fitness must be verified, contact manufacturer for information (refer to Product overview and Resistance list).

12.423 / 12.463 PN16 EN-JL1040 DN200-250
22.423 / 22.463 PN16 EN-JS1049 DN200-250
22.423 PN16 EN-JS1049 DN300
34.423 / 34.463 PN25 1.0619+N DN200-250
35.423 / 35.463 PN40 1.0619+N DN200-250
Other materials and versions on request.
 

Pressure-temperature-ratings

Intermediate values for max. permissible operational pressures can be determined by linear interpolation of the given temperature / pressure chart.
acc. to DIN EN 1092-2 -60°C to <-10°C 1) -10°C to 120°C 150°C 200°C 250°C 300°C 350°C 400°C 450°C
EN-JL1040 PN16 (bar) 16 14,4 12,8 11,2 9,6
EN-JS1049 PN16 (bar) on request 16 15,5 14,7 13,9 12,8 11,2
acc. to DIN EN 1092-2 -60°C to <-10°C 1) -10°C to 120°C 150°C 200°C 250°C 300°C 350°C 400°C 450°C
EN-JL1040 PN16 (bar) 16 14,4 12,8 11,2 9,6
EN-JS1049 PN16 (bar) on request 16 15,5 14,7 13,9 12,8 11,2
acc. to DIN EN 1092-1 -60°C to <-10°C 1) -10°C to 100°C 150°C 200°C 250°C 300°C 350°C 400°C 450°C
1.4408 PN40 (bar) 40 40 36,3 33,7 31,8 29,7 28,5 27,4