Description
eClass-No.: | 37010201 |
Application: | Selection criteria: boiler blow down Application: steam boiler engineering |
Medium: | Cooling water, cooling brine, warm water, hot water, steam, gas, etc. |
ARI-STEVI®BBD 415 (DN25 – 50)
Pneumatic actuator
• Required air supply pressure max. 6 bar
• Options:
– Assembly of additional devices
– Lever
Operating principles
The steam trap is controlled by a swivel-mounted ball float (Pos. 24.16).
An integral bimetallic element (Pos. 24.6) provides automatic starting ventilation in the cold state.
At temperatures less than 90°C, the bi-metallic element holds the discharge orifice open, allowing air and other gasses to escape. At 90°C the bi-metallic element is fully closed and discharge is controlled only by the float mechanism (Pos. 24.16).
At the higher temperatures, air is automatically evacuated (Pos. 24.12), ejector style, with the condensate.
If the amount of condensate decreases or if there is no condensate, the ball float (Pos. 24.16) faces and locks the valve ball (Pos. 24.4) on the seat (Pos. 24.1). If the steam trap is acted upon only by vapour, the condensate-flooded seat (Pos. 24.1) remains shut.
The valve ball (Pos. 24.4) also works with the seat (Pos. 24.1) as a non-return valve.
Technical data
Figure | Nominal pressure | Material | Nominal diameter | Information / restriction of technical rules need to be observed! A production permission acc. to TRB 801 No. 45 is available.
The engineer, designing a system or a plant, is responsible for the selection of the correct valve. Resistance and fitness must be verified (contact manufacturer for information, refer to Product overview and Resistance list). |
35.415 | PN40 | 1.0619+N | DN 25 – 50 | |
Other materials and versions on request. |
Stem sealing | |
Fig. 415 | standard |
![]() |
|
I. PTFE-V-ring unit
-10°C to 240°C |
Pressure-temperature-ratings |
Intermediate values for max. permissible operational pressures can be determined by linear interpolation of the given temperature / pressure chart. |
acc. to manufacturers standard | -10°C to 120°C | 150°C | 200°C | 250°C | 300°C | 350°C | 400°C | 450°C | ||
1.0619+N | PN40 | (bar) | 40 | 38,1 | 35 | 32 | 28 | 25,7 | 23,8 | 13,1 |
DN | 25 | 32 | 40 | 50 | |
Seat-Ø | (mm) | 22 | 27 | 37 | 47 |
Travel | (mm) | 8 | 7 | 10 | 13 |
Kvs-value | |||||
standard | (m3/h) | 6,4 | 6,4 | 14,7 | 14,7 |
Face-to-face dimension FTF series 1 according to DIN EN 558 | |||||
L | (mm) | 160 | 180 | 200 | 230 |
Flanges acc. to DIN EN 1092-1/-2 | Flange holes / -thickness tolerances acc. to DIN 2533/2544/2545 | |||||
Ø D | PN40 | (mm) | 115 | 140 | 150 | 165 |
Ø K | (mm) | 85 | 100 | 110 | 125 | |
n x Ø d1 | (mm) | 4 x 14 | 4 x 18 | 4 x 18 | 4 x 18 |
Dimensions | |||||
H | (mm) | 336 | 336 | 364 | 370 |
Ø A | (mm) | 168 | 168 | 250 | 250 |
G | (inch) | 1/4“ | 1/4“ | 1/4“ | 1/4“ |
Weight | |||||
35.415 | (kg) | 13 | 15 | 18,3 | 21,5 |
ARI-STEVI®BBD 415 (DN25 – 50)
Blow down valve – straight through with flanges and pneumatic actuator
PHONE: 0812-3340-4116WHATSAPP: 0812-3340-4116
ARI ARMATUREN – Steam product solutions
- ARI-STEVI® Pro 470 / 471 (DN15-150) Control valve
- ARI-STEVI® Pro 470 / 471 – ANSI (DN25-200) Control valve
- ARI-STEVI® Pro 422 / 462 (DN200-250) Control valve
- ARI-STEVI® Vario 448 / 449 (DN15-100) Control valve
- ARI-STEVI® 440 / 441 (DN15-250) Control valve ARI Armaturen
- ARI-STEVI® 425 / 426 (DN300-500) Control valve ARI Armaturen
- ARI-STEVI® 450 / 451 (DN15-150) Control valve
- ARI-STEVI® Smart 423 / 463 (DN200-300) Control valve
- ARI-STEVI® Pro 453 Feedwater control valve
- ARI-STEVI® 405 / 460 (DN15-500) Stop valve
- ARI-STEVI®BBD 415 (DN25 – 50) Blow down valve