LCS3050

Low Water Level Switch for two probes

Pressure Equipment Directive (PED) 2014/68/EU
Water level limiters are safety accessories as defined in the Pressure Equipment
Directive (PED).
The level switch LCS3050 in conjunction with level probe LP40 are EU type approved according to EN 12952/EN 12953.
These Directives state,
among other things, the requirements made on limiting systems and equipment for steam boiler plants and (pressurised) hot-water installations.

Functional Safety acc. to IEC 61508
The level switch LCS3050 is certified acc. to IEC 61508 only if used in
combination with level probe LP40.
This standard describes the functional safety of safety-related electrical/electronic/programmable electronic systems.
The equipment combination LP40 + LCS3050 corresponds to a type B subsystem
with Safety Integrity Level (SIL) 3.

VdTÜV Bulletin “Wasserstand 100” (Water Level 100)
The level switch LCS3050 in conjunction with the level probe LP40 is type approved according to the VdTÜV Bulletin “Water Level 100”.
The VdTÜV Bulletin “Wasserstand (Water Level) 100” specifies the requirements made on water level control and limiting equipment for boilers.

LV (Low Voltage) Directive and EMC (ElectromagneticCompatibility)
The level switch LCS3050 meets the requirements of the Low Voltage Directive 2014/35/EU and the EMC Directive 2014/30/EU.

ATEX (Atmosphère Explosible)
According to the European Directive 2014/34/EU the level switch LCS3050 must not be used in potentially explosive areas.

– Steam boilers
– Pressurised hot-water plants

Supply voltage 24 Vdc +/- 20%
Fuse External 0.5 A (semi-delay)
Power consumption 7 W
Electrical connection of level probe 2 inputs for level probe LP40, 4 poles, with screen
Response sensitivity (electrical conductivity of water at 25 °C) > 10 … < 10000 μS/cm
Safety circuit 2 volt-free make contacts, 6 A 250 Vac/30 Vdc cos f = 1
Delay of response: 3 seconds
Provide inductive loads with RC combinations according to manufacturer’s specification to ensure interference suppression
Signal output 2 volt-free outputs for instantaneous external signalling, 24 Vdc, max. 100 mA (semiconductor output)
Indicators and adjustors 2 buttons for test and diagnosis
2 red/green LEDs for indicating the operating mode and alarm
3 red LEDs for diagnosis
2 two-pole code switches for setting the number of probes
Housing Housing material: base: black polycarbonate; front: grey polycarbonate
Conductor size: 1 x 4.0 mm2 solid per wire or
1 x 2.5 mm2 per stranded wire with sleeve to DIN 46228 or
2 x 1.5 mm2 per stranded wire with sleeve to DIN 46228
Terminal strips can be detached
Fixing of housing: Mounting clip on supporting rail TH 35, EN 60715
Electrical safety Degree of contamination: 2, overvoltage category III to EN 61010-01
Protection Housing: IP 40 to EN 60529
Terminal strip: IP 20 to EN 60529
Weight approx. 0.5 kg
Ambient temperature At moment of switch on: 0 ° to 55 °C
In operation: -10° to 55 °C
Transport temperature -20 to +80 °C (<100 hours), defrosting time of the de-energized equipment before it can be put into operation: 24 hours
Storage temperature -20 to +70 °C, defrosting time of the de-energized equipment before it can be put into operation: 24 hours
Relative humidity max. 95%, no moisture condensation
Site altitude max. 2000 m

LCS3050 Low Water Level Switch for two probes

Item
1 Supply voltage
2 Signal output 1/2 for external alarm 24 Vdc, 100 mA (semiconductor output)
3 Safety circuit, input and output
4 Wire link, on site, when used as water level limiter according to EN 12952 / EN 12953
5 CEP Central earthing point in control cabinet
6 Level probe LP40