Description
Features
• 2 torque switches
• Handwheel
• Operative ambient temperatures -20 °C up to +70 °C
• Enclosure IP 65
• Additional devices available, e.g. potentiometer
• Travel indicator
Technical data ARI-PREMIO® 2,2 – 5 KN
Type | ARI-PREMIO® 2,2 kN | ARI-PREMIO® 5 kN | ||
Thrust force | kN | 2,2 kN | 5,0 kN | |
Operating speed | mm/s | 0,38 mm/s | 0,25/0,38/0,47/1,0 mm/s
adjustable |
|
Travel distance max. | mm | 50 mm | ||
Duty classification in accordance with EN 60034-1 | S3 80 % ED/max. 1200 c/h (at 70 °C) | |||
Supply voltage | V – Hz | 230 V – 50/60 Hz | 24 V AC/DC | |
Motor type | Synchronous motor | BLDC (Brushless DC motor) | ||
Power consumption | VA | 21 | max. 22 | max. 65 |
Current consumption | A | approx. 0,1 A | approx. 1 A | approx. 2,5 A |
Torque switch | 2 pcs., fixed wiring switching capacity 10 A, 250 V~ | |||
Travel switch | 1 pc., fixed wiring switching capacity 10 A, 250 V~ (Options trip slide necessary!) | |||
Enclosure EN 60529 | IP 65 | |||
Max. storage temperature | °C | -40 °C … +85 °C | ||
Max. permissible ambient temperature | °C | -20 °C … +70 °C, for UL/CSA version up to max. +60 °C
(For outdoor use and sub-zero temperatures, a heating is recommended!) |
||
Hand operating device | Yes (always running) | |||
Operation | 3-point –
Response time up to 100 ms |
3-point –
Response time approx. 80 ms |
||
Max. cable cross section | mm2 | 3-point-input: 2,5 mm2 | ||
Cable diameter for cable glands | 2 x M16 x 1,5: 5 – 9,5 mm | |||
Electrical safety according to DIN EN 61010, part 1 | Overvoltage category II
Pollution degree 2 Altitude up to 2000 m Rel. humidity ≤ 90 % non-condensing |
|||
Mounting position | Any, except: motor not hanging downwards | |||
Gear lubricant | Klüber Isoflex Topas NB152 | |||
Weight | kg | 5,8 kg |
Additional voltage / frequencies
Type | 100 – 240 V AC switching power supply
for BLDC version |
||
Thrust force | kN | 2,2 kN | 5,0 kN |
Input voltage | V – Hz | 3-point signal: 100 – 240 V AC 50/60 Hz | |
Output voltage | V | 24 V DC | |
Output signal | 3-point (TTL technology) | ||
Current consumption max. | A | max. 0,4 A at 230 V/0,6 A at 115 V | |
Response time | ms | approx. 400 ms |
Type |
3~ 400 V transformer
for BLDC version with direction detection and 3-point-output |
||
Thrust force | kN | 2,2 kN | 5,0 kN |
Input voltage | V – Hz | UVW: 3~ 400 V – 50/60 Hz | |
Output voltage | V | 3-point signal: 24 V DC | |
Current consumption max. | A | max. 0,13 A | |
Response time | ms | < 10 ms |
Technical data ARI-PREMIO® 12 – 25 KN
Type | ARI-PREMIO® 12 kN | ARI-PREMIO® 15 kN | ARI-PREMIO® 25 kN | |
Thrust force | kN | 12,0 kN | 15,0 kN | 25,0 kN |
Operating speed | mm/s | 0,20/0,31/0,38/0,79 mm/s
adjustable |
||
Travel distance max. | mm | 80 mm | ||
Duty classification in accordance with EN 60034-1 | S3 80 % ED/max. 1200 c/h (at 70 °C) | |||
Supply voltage | V – Hz | 24 V AC/DC | ||
Motor type | BLDC (Brushless DC motor) | |||
Power consumption | VA | max. 65 (depending on the operating speed and operating force) | max. 130 (depending on the operating speed and operating force) | |
Current consumption | A | approx. 2,5 A | approx. 5 A | |
Torque switch | 2 pcs., fixed wiring switching capacity 16 A, 250 V ~ | |||
Travel switch | 1 pc., fixed wiring switching capacity 16 A, 250 V ~ (Options trip slide necessary!) | |||
Enclosure EN 60529 | IP 65 | |||
Max. storage temperature | °C | -40 °C … +85 °C | ||
Max. permissible ambient temperature | °C | -20 °C … +70 °C, for UL/CSA version up to max. +60 °C
(For outdoor use and sub-zero temperatures, a heating is recommended!) |
||
Hand operating device | Yes (engageable) | |||
Operation | 3-point – Response time approx. 80 ms | |||
Max. cable cross section | mm2 | 3-point-input: 2,5 mm2 | ||
Cable diameter for cable glands | 2 x M16: 5 – 9,5 mm 1 x M20: 8 – 13 mm | |||
Electrical safety according to DIN EN 61010, part 1 | Overvoltage category II
Pollution degree 2 Altitude up to 2000 m Rel. humidity ≤ 90 % non-condensing |
|||
Mounting position | Any, except: motor not hanging downwards | |||
Gear lubricant | Klübersynth G34 – 130 | |||
Weight | kg | 10,0 kg | 11,0 kg |
Additional voltage / frequencies
Type | 100 – 240 V AC switching power supply | |||
Thrust force | kN | 12,0 kN | 15,0 kN | 25,0 kN |
Input voltage | V – Hz | 3-point signal: 100 – 240 V AC 50/60 Hz | ||
Output voltage | V | 24 V DC | ||
Output signal | 3-point (TTL technology) | |||
Current consumption max. | VA | max. 1 A at 230 V/
1,8 A at 115 V |
max. 1,1 A at 230 V/
1,9 A at 115 V |
|
Response time | ms | approx. 240 ms | approx. 350 ms |
Type | 100 – 240 V AC switching power supply | |||
Thrust force | kN | 12,0 kN | 15,0 kN | 25,0 kN |
Input voltage | V – Hz | 3-point signal: 100 – 240 V AC 50/60 Hz | ||
Output voltage | V | 24 V DC | ||
Output signal | 3-point (TTL technology) | |||
Current consumption max. | VA | max. 1 A at 230 V/
1,8 A at 115 V |
max. 1,1 A at 230 V/
1,9 A at 115 V |
|
Response time | ms | approx. 240 ms | approx. 350 ms |
ARI-PREMIO® 2,2 – 5 kN / 12 – 25 kN
Electric actuator
PHONE: 0812-3340-4116WHATSAPP: 0812-3340-4116
ARI ARMATUREN – Steam product solution
- ARI-CODI B (AWH) PN40 / PN63 ARI Armaturen
- ARI-PREMIO® 2,2 – 5 kN / 12 – 25 kN Electric actuator
- ARI-PREMIO®-Plus 2G Thrust actuator ARI Armaturen
- ARI-CODI S (AWH) PN40 / PN63 ARI Armaturen
- Double window sight glasses (AWH) PN16 / PN40 ARI Armaturen
- ARI-CONA 650 (AWH) Liquid return temperature limiter PN40
- ARI-CONA 645/647 Condensate discharge temperature limiter (AWH) PN40