Electromagnetic Flow Converter with Thermal Energy Model AMC3200E Series
Description
AMC3200E Series is a heat meter converter of electromagnetic flowmeter that can be paired with any of ALIA AMF series sensors.
The unit features multiple display parameters including flow rate, energy, flow total, energy total, supply temperature, return temperature, diagnostic, programming and troubleshooting.
It’s equipped with MODBUS, Bluetooth and BACnet protocol.
Feature
- Four line LCD display Flow Rate / Energy / Totalizer / Temperature
- +/-0.2% value of reading
- Bi-direction flow measurement, and the display can rotate
- With hourly report, daily report, monthly report and yearly report
- query function
- 99 times / dates records for alarm
- 99 (total) times records for power on / off
- MODBUS, Bluetooth, BACnet protocol
Specification
Excitation | DC pulsed |
Display | 4 Lines LCD with backlight
Line 1: Date and Time Line 2: 5 Digit flowrate Line 3: 9 Digit totalizer for forward flow / reverse flow Line 4: Differential temperature Unit: L/s, L/min, L/hr, m3/s, m3/min, m3/hr, mL/hr, mL/min, mL/s, kW, MW, KJ/hr, MJ/hr, GJ/hr, Mcal/hr, Kcal/hr, Cal/hr, BTU/hr |
Measuring Range | Min. 0-0.15 m/s Max. 0-15 m/s |
Accuracy | +/-0.2% of reading (Velocity≥0.5 m/s) +/-0.001 m/s (Velocity<0.5 m/s) |
Repeatability | +/-0.05% of reading |
Current Output | 4-20 mA (Isolated) Load: Max. 600 Ω |
Pulse Output | Open collector Rating: 3-30 VDC, 50 mA Max. |
Pulse Rate | 1) Scaled pulse, (L/Pulse, Other) 2) Frequency: 0-5000 Hz |
Communication | Bluetooth (Apply to Android System) RS485 (MODBUS Protocol) / BACnet |
Keypad | 3 External keys for programming and display control |
Low Flow Cut-off | 0-9.9% |
Data Logger Function | 99 Date / time records for alarm |
Record Data | Date / time of power on/off
99 Years flow rate / energy / temperature / total flow / total energy |
Damping | 0.1-99.9 s |
Self Diagnosis | The following error messages are displayed if failure occurs – Temperature failure – Temperature abnormal – Empty pipe – EEPROM abnormal |
Data Storage | Operation parameters and totalization figures are stored by EEPROM for more than 10 years |
Cable Entry | Standard: M20 Option: 1/2″ NPTF |
Protection Class | IP67 |
Ambient Temperature | -25-65 oC |
Material | Aluminium Alloy |
Temperature Input | PT1000, 2 wires |
Power Supply | 90-260 VAC, 50/60 Hz 24 VDC +/-10% (Option) |
Power Consumption | 10-20 W (Dependent on sensor size) |
Weight | 4.5 kg |
Mounting | Bracket on 2″ pipe |
Download PDF
ALIAMAG AMC3200E Series, ALIA Liquid Flow Meter in Surabaya Indonesia, Model dan Tipe Flowmeter Electromagnetic Alia, Flowmeter Electromagnetic Alia AMC 3200E Series, Indonesian Distributor ALIA Group inc.