The temperature switch TRS 5-50 is used in conjunction with temperature sensor TRG 5-6.. as safety temperature limiter or monitor, for instance in steam boilers and (pressurised) hot-water plants. When the max. admissible temperature in the superheater or the inlet line is reached, the safety temperature limiter or monitor switches the heating off.

The temperature switch TRS 5-52 is designed for use in conjunction with temperature sensors TRG 5-63, TRG 5-64, TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68

A platinum resistance thermometer Pt 100 to EN 60751 is used as temperature sensor for the temperature switch TRS 5-50. A three-wire configuration is used for the electrical connection.

The temperature switch processes the temperature-dependent changes in resistance of the temperature sensor and, during normal operation, the seven-segment LED display shows the adjusted switch-off temperature TMAX (°C) and the actual value T (°C). The switchpoint for MAX temperature can be variably adjusted within the measuring range. Once the MAX temperature is reached

both output contacts of the temperature switch open the safety circuit and the seven-segment LED display for TMAX is flashing.

In addition the relay contact for external signalling equipment is closed.

If the system is configured as safety temperature monitor, the temperature switch does not automatically interlock the deactivation of the heating. As soon as the temperature has fallen below the non-adjustable hysteresis, the safety circuit will be closed again.

However, if the system is configured as safety temperature limiter, the temperature switch automatically interlocks the de- activation of the heating. Note that once the temperature has fallen below the non-adjusted hysteresis, the equipment must be reset manually or externally in order to close the safety circuit.

Any error or malfunction that occurs in the temperature sensor, the electrical connection or the temperature switch is indicated by the seven-segment LED display and the output contacts will be opened.

An automatic self-testing routine monitors the safety functions in the temperature switch and the temperature sensor. In the event of a malfunction the safety circuit opens instantaneously and switches the heating off.

Parameter settings can be changed, a MAX temperature alarm can be simulated and the equipment can be reset by operating the rotary button.

For external temperature indication the equipment is optionally available with an actual-value output 4-20 mA.

Functional Safety acc. to IEC 61508

Safety characteristics of the subsystem TRG 5-6.. / TRS 5-50

The equipment combination TRG 5-6.. / TRS 5-50 corresponds to a type B subsystem with Safety Integrity Level (SIL) 3. Type B means that the behaviour under fault conditions of the used components cannot be completely determined. The functional safety of the equipment combination refers to the detection and evaluation of the temperature and, as a consequence, the contact position of the output relays.

The design of the equipment combination TRG 5-6.. / TRS 5-50 corresponds to the architecture 1oo2. This architecture consists of two channels that detect and diagnose faults in each other. If a fault is detected, the equipment combination TRG 5-6.. / TRS 5-50 will go to the safe state, which means that the contacts of both output relays will open the safety circuit.

The equipment is suitable for machines and installations up to performance level “e”.

Safety characteristics SIL Architecture Life time (a) Proof Test Interval (a)
General 3 1oo2 20 20
SFF PFDav PFHav l DU
Temperature switch TRS 5-50 (alone) 99.6 % 2.69 x 10-5 3.07 x 10-9 2.95 x 10-9 / h
Temperature switch TRS 5-50 in conjunction with one temperature sensor TRG 5-6.. 98.2 % 1.71 x 10-4 1.96 x 10-8 1.95 x 10-8 / h
Terms / Abbreviations Description
Safety Integrity Level SIL Classification of the Safety Integrity Level acc. to IEC 61508
Life time (a) Functional safety: Life time of equipment combination in years
Safe Failure Fraction SFF Percentage of failures without the potential to put the safety-related system into a dangerous state
Probability Failure per Demand (Low Demand) PFDav Average probability of failure on demand for low demand mode (once a year)
Probability Failure per Hour PFHav Probability of failure per hour
l DU Failure rate for all dangerous undetected failures (per hour) of a channel of a subsystem

Determination of the Safety Integrity Level (SIL) for safety-related systems

Temperature sensor, temperature switch and actuators (auxiliary contactor in safety circuit) are subsystems and together constitute a safety-related system that executes a safety function.

The specification of the safety-related characteristics refers to the temperature sensor and the temperature switch including the output contacts. The actuator (e. g. an auxiliary contactor in the safety circuit) is installation specific and, according to IEC 61508, must be considered separately for the whole safety-related system.

Supply voltage

24 VDC +/– 20%, 0.3 A;

100-240 VAC + 10 / – 15%, 47-63 Hz, 0.2 A

Fuse

external 0.5 A (semi-delay)

Power consumption

7 VA

Connection of temperature sensor

1 input for temperature sensor TRG 5-63, TRG 5-64,

TRG 5-65, TRG 5-66, TRG 5-67 and TRG 5-68,

(platinum resistance thermometer Pt 100 to EN 60751) , 3 poles with screen.

Connection for external test & reset

volt-free input, 24 VDC, for connecting external reset and test button.

Safety circuit

2 volt-free make contacts,
6 A 250 V AC / 30 V DC cos
ϕ = 1
(external slow-blow fuse 2 A)
Provide inductive loads with RC combinations according
to manufacturer’s specification to ensure interference
suppression.
1 analogue output 4-20 mA (0 – 650 °C), max. load
500 ohm, e. g. for actual-value indication (optional)

Signal output

1 volt-free output for instantaneous external signalling, 24 V DC, max. 100 mA (semiconductor output)

Limit range

  • °C up to 600 °C

Switching hysteresis

Switchpoint for MAX temperature -2 °C, fixed setting.

Indicators and adjusters

  • rotary button with integrated pushbutton for setting the MAX temperature and testing and resetting the 1 pushbutton (hidden) for enabling the setting.
  • seven-segment three-digit LED dispaly for MAX tempe- rature and actual value

Housing

Housing material: base: polycarbonate, black; front: polycarbonate, grey

Conductor size: 1 x 4.0 mm2 solid per wire or

1 x 2.5 mm2 per stranded wire with sleeve to DIN 46228 or 2 x 1.4 mm2 per stranded wire with sleeve to DIN 46228 terminal strips can be detached separately

Fixing of housing: Mounting clip on supporting rail TH 35, EN 60715

Electrical safety

Pollution degree 2, overvoltage category III to EN 61010-01

Protection

Housing: IP 40 to EN 60529 Terminal strip: IP 20 to EN 60529 Weight

Approx. 0.5 kg

Ambient temperature

when system is switched on: 0 … 55 °C, during operation: –10 … 55 °C Transport temperature

–20 … +80 °C (<100 hours), defrosting time of the de-energized equipment before it can be put into operation: 24 hours. 24 hours.

Storage temperature

–20 … +70 °C, defrosting time of the de-energized equipment before it can be put into operation:

24 hours.

Relative humidity

max. 95%, no moisture condensation

Site altitude

max. 2000 m

Are you searching for a reliable, accurate, and industry-proven temperature switch for your industrial operation? The GESTRA TRS 5-50 Temperature Switch stands as one of the most trusted instruments worldwide for precision temperature control, safety automation, and thermal protection. Engineered to meet the most demanding industrial standards, this device delivers consistent performance even in harsh and high-pressure environments.

The GESTRA TRS 5-50 Temperature Switch is a high-accuracy thermal monitoring device designed specifically for industrial temperature measurement and safety control. It ensures reliable switching functions based on preset temperature thresholds, making it ideal for steam systems, boilers, heat exchangers, pipelines, and various thermal process installations.

With decades of proven performance, GESTRA has positioned the TRS 5-50 as a top-tier choice for critical temperature regulation.

Investing in the TRS 5-50 means choosing long-term reliability and outstanding precision. Key features include:

High Temperature Accuracy

Designed for environments requiring exact and stable temperature readings.

Robust Industrial Construction

Built using corrosion-resistant materials to guarantee durability in demanding applications.

Fast Response Time

Detects temperature fluctuations instantly—ideal for safety and emergency shutdown systems.

Easy Integration

Compatible with various GESTRA control systems and other industrial automation platforms.

Wide Temperature Range

Engineered to monitor a wide thermal spectrum, suitable for numerous industrial processes.

Low Maintenance Requirement

Designed for long service life, reducing operational downtime and maintenance cost.

The GESTRA TRS 5-50 stands out for its unmatched precision and reliability. Here’s why industries around the world trust this product:

Proven Performance in Harsh Conditions

It maintains stable performance even in high-pressure steam environments.

Enhanced Plant Safety

Accurate switching reduces the risk of overheating, system failures, and operational hazards.

Energy Efficiency

Optimal temperature regulation contributes to better energy management.

Compatible with Global Industrial Standards

Suitable for industrial facilities requiring top-quality safety and control instruments.

The TRS 5-50 is widely used across various industries:

  • Boiler and Steam Systems

  • Power Plants

  • Chemical and Petrochemical Industries

  • Oil & Gas Processing

  • Manufacturing Plants

  • HVAC and Thermal Management Systems

  • Food and Beverage Production

Its versatility makes it a go-to temperature switching device for engineers and automation specialists.

The GESTRA TRS 5-50 includes highly engineered components that deliver:

  • Precision switching under fluctuating temperature loads

  • Long-lasting thermal sensors

  • Stable performance unaffected by electromagnetic interference

  • Compact and lightweight design for easy installation

  • Reliability guaranteed by GESTRA’s German engineering excellence

We offer 100% original GESTRA products, competitive pricing, and fast delivery.
If you need technical consultation or product recommendations, our expert team is ready to help.

👉 Contact us today to receive the best quote for the GESTRA TRS 5-50 Temperature Switch!

©2022 PT. TOTALITAS TEKNIK INDONESIA. All Rights Reserved.