Diskripsi Produk
The AUL730 Series is a fixed mounted, Ultrasonic Level Transmitter with Fix-in the air and used for non-invasive measurement.
Our microprocessor based, user friendly, field programmable level measurement technique allows no interruption of the process level and has low installation costs.
Fitur
- Simple set-up and operation
- Fast and simple to install and configure
- Loop-powered 4-20 mA output with HART signal
- Low cost of installation and commissioning
- Non-contact level measurement
- Exclusive sensor for level transmitter
- Response time less than 1 second
Spesifikasi
Measuring Principle | : | Ultrasonic Level Measurement |
Measuring Range | : | 0-3 m, 0-5 m, 0-10 m, 0-15 m, 0-20 m |
: | 0-10 ft, 0-16 ft, 0-33 ft, 0-50 ft, 0-65 ft | |
Display | : | 4 Line LCD with Bargraph (illumination) |
Resolution | : | 1 mm / 0.003 ft |
Accuracy | : | +/-0.25% of Full Scale |
Repeatability | : | +/-0.1% of reading |
Material | ||
Ultrasonic Tube | : | ABS |
Sensor Head | : | Polyurethane (Standard) / ETFE / PTFE |
Housing | : | ABS or Aluminum Alloy (Weather Proof) |
: | Aluminum Alloy (Explosion Proof) | |
Update Time | : | <3 s |
Ambient Temperature | : | -20~60 °C |
Relative Humidity | : | 0-100% RH |
Sensor Frequency | : | 40 kHz / 1 kHz |
Blanking Distance | : | 0.35-1.0 m |
Bean Angle | : | 6° |
Keypad | : | 4 Key with tactile action |
Response Time | : | Less than 1 second |
Protection Class | : | IP65 (ABS) / IP67 (Aluminum Alloy) |
: | Explosion Proof, Ex d (ia) IIB T4 | |
Installation | : | G 2″ and 20 m sensor is M70 * 2 Standard |
: | Flange end (Optional) | |
EMI / RFI Effect | : | Follow SAMA PMC 33.1 from 20-1000 |
MHz and for field strengths up to 30 V/m |
Process Temperature | : | -40~60 °C (Standard) |
: | -40~100 °C (Optional) | |
Process Pressure | : | -0.8~2.0 bar G |
Max. Cable Length | : | 50 Meter (Remote Version) |
Power Supply | : | 12-36 VDC (2 wires) (Compact) |
: | Start-up current 25 mA (Standard) | |
: | Start-up current 40 mA (With HART) | |
: | 12-36 VDC / 85-260 VAC, 4 wires (Remote) | |
Power Consumption | : | Less than 3W |
Current Output | : | 4-20 mA (2 wires, 4 wires) |
Load | : | Rohm= (VDC-12) * 50 W |
Alarm Output | : | High/Low/High-High/Low-Low (Remote) |
Communication | : | RS485 MODBUS, 4 wires only (Standard) |
: | HART Signal (Optional) | |
Temp. Compensation | : | Built-in to compensate over temperature |
range | ||
Data Storage | : | Operation parameters are stored by |
EEPROM for more than 10 years | ||
Dimensions | ||
Compact (ABS) | : | 105 mm (W) * 262 mm (H) * 168 mm (D) |
Compact (Aluminum) | : | 161 mm (W) * 247 mm (H) * 132 mm (D) |
Remote (ABS) | : | 183.5 mm (W) * 218 mm (H) * 125.5 mm (D) |
Weight | : | 1.0 kg / 2.2 kg (Compact), 2.2 kg (Remote) |